NYY-J (HIGH-TUFF)
NYY-J Cable Current Carrying Capacity Chart
The table below shows the current-carrying capacities of NYY-J PVC insulated and sheathed power cables, based on published technical data.
Ratings are provided for different conductor sizes and numbers of cores, with a distinction between installation in air and installation in ducts.
NYY-J Current Carrying Capacity (Amperes)
| Conductor Size (mm²) | 2-Core In Air / In Duct | 3 & 4-Core In Air / In Duct | 5-Core In Air / In Duct |
|---|---|---|---|
| 1.5 | 20A / 32A | 18A / 26A | 18A / 24A |
| 2.5 | 27A / 42A | 25A / 34A | 25A / 34A |
| 4 | 37A / 54A | 34A / 44A | 34A / 44A |
| 6 | 48A / 68A | 43A / 56A | 43A / 56A |
| 10 | 66A / 90A | 60A / 75A | 60A / 75A |
| 16 | 89A / 116A | 80A / 98A | 80A / 98A |
Understanding Installation Methods
In Air: Refers to cables installed in air under the reference conditions specified in the manufacturer's technical data. Actual current-carrying capacity may vary depending on cable arrangement, ventilation, ambient temperature and grouping.
In Duct: Refers to the duct installation conditions used in the manufacturer's published ratings. These figures must not be assumed to apply to all conduit, trunking or enclosed installations.
Underground Installation: NYY-J cable can be suitable for direct burial or installation in underground ducts. However, current-carrying capacity depends on factors including burial depth, soil thermal resistivity, ground temperature and cable grouping. The duct figures above must not automatically be used as underground installation ratings.
Important Installation & Safety Disclaimer
The current-carrying capacities shown are for guidance only and must not be used as universal cable ratings.
Actual current-carrying capacity depends on several factors, including:
-
Installation method and cable arrangement
-
Ambient air or ground temperature
-
Cable grouping and spacing
-
Thermal insulation and heat dissipation
-
Burial depth and soil thermal resistivity
-
Number of loaded conductors
-
Applicable correction and derating factors
Cable selection and circuit design must comply with the current edition of BS 7671 (IET Wiring Regulations). Installers should refer to the manufacturer's technical datasheet and applicable installation-method tables to establish the correct current-carrying capacity for the specific installation.
If you are in any doubt about cable selection, current-carrying capacity or the appropriate installation method, always consult a qualified electrician before proceeding.
Order Electrical accepts no responsibility for incorrect cable selection or installation based solely on the indicative ratings provided above.